技術(shù)要求1、試驗(yàn)變壓器使用環(huán)境要求:1.1輸入電壓:交流220V或380V,50Hz;1.2環(huán)境溫度:-40℃~40℃;1.3相對(duì)濕度: 85%(環(huán)境溫度為25℃時(shí));1.4不含有化學(xué)性氣體及蒸汽的環(huán)境中;1.5無爆炸性危險(xiǎn)的氣體中;1.6不受雨水浸入的場(chǎng)合下。2、技術(shù)參數(shù) 型號(hào)規(guī)格容量KVA低壓輸入交流高壓輸出直流高壓輸出 kV測(cè)量 變比電壓 V電流 A電壓 kV電流 mAYDJ-1.5/501.52007.5503070500YDJ-3/50320015506070500YDJ-5/505200255010070500YDJ-10/5010200505020070500YDJ-20/5020400285040070500YDJ-30/5030400435060070500YDJ-50/50504007250100070500YDJ-10/10010200501001001401000YDJ-20/10020400281002001401000YDJ-30/10030400431003001401000YDJ-50/10050400721005001401000YDJ-100/10010040014410010001401000YDJ-20/15020400281501332101000YDJ-30/15030400431502002101000YDJ-50/15050400721503332101000YDJ-100/1501004001441506662101000YDJ-150/15015040021615010002101000YDJ-50/2005040072200250 1000YDJ-100/200100400144200500 1000YDJ-200/2002004002882001000 1000YDJ-50/3005040072300166 1000YDJ-100/300100400144300333 1000YDJ-200/300200400288300666 1000YDJ-300/3003004004333001000 1000注:1、我公司YDJ系列試驗(yàn)變壓器單臺(tái)可做到交流350kV,容量300kVA;2、如果用戶需要,我廠生產(chǎn)的YDJ系列試驗(yàn)變壓器,抽出200V的串級(jí)抽頭,串級(jí)高壓試驗(yàn)變壓器串級(jí)試驗(yàn)變壓器可將二臺(tái)或三臺(tái)串級(jí)成交流100kV、150kV、200kV、350kV的高電壓。也可根據(jù)用戶的需要,在高壓繞組中抽出5~15kV的中壓抽頭,供高壓電機(jī)作交流耐壓試驗(yàn);3、表格中 直流高壓輸出 一欄,為交直流兩用試驗(yàn)變壓器的直流高壓輸出值;4、我公司還可根據(jù)用戶的要求,定制各種特殊規(guī)格的高壓試驗(yàn)變壓器。